InetSupervisor product suite Installation kits. Prerequisites: 1. Install IIS - Control Panel/Add Remove Programs/Add Remove Windows Components/IIS 2. Install .NET Framework version 2.0 and 3.5sp1 - Use windows update. Installation order is: 1. DatabaseServer 2. DatabaseConfig (Log in and run the Configure/SQL Server/Verify DB Structure) 3. All other required kits The DatabaseServer installation kit will install Microsoft SQL Server 2005 desktop edition on you PC. Use this kit only if you don't already have the MS Sql Server (default instance) installed on the PC. LNSDriverService is an LonWorks LNS Turbo 3.2 or later system driver. Use LNSConfig to configure it. BACnetDriverService is a BACnet over IP driver. iLON100SoapDriver is an iLON100 Trends backup driver. Backup trends from i.Lon to InetSupervisor SQL Server database. To install the kits you must unzip (using WinRar from RARLabs.com, its free) the kits into a temporary directory. Burn a CD then use it for installation; alternatively you can run installers from you hard drive by double-click on the Launch.exe. Please note that you must use the Launch.exe to run installers as it performs many installation functions. The CD Browser will automatically start on 'CD insert' and lead you through the installation. ***************** ***************** Fixes/Changes ******************************************************************************** FUTURE RELEASE InetSupervisor release date: xxxx InetSupervisor version: xxxx Concentrator ServiceAtlas xxxx DBConfig xxxx InetDriver xxxx LNCConfig xxxx LNSDriverService xxxx ModbusDriver xxxx OPCConfig xxxx OPCDriverService xxxx TitanSDKService xxxx Modbus Driver: added functionality to read IEEE754 32bit, single precision floating point numbers by adding parameter “2,2”. I also added functionality to read/write Unsigned 32bit integer values by adding parameter “2,3”. HMIweb exposed connection string for schedules, now can point to another sql server. Updated to .NET4.0; Schedules one-time-exception includes logicName of the scheduled point. Trend viewer is modified to show list of points using LogicName from the latest trends samples and is sorted alphabetically. InetTEAM - fixed hardcoded IP addresses , so now it can run on one PC but use sql database from another. Modbus Driver: now the COMM port is done through .net framework driver. Added ReadArgs handling , so the read values can be manipulated by PointEditor Read Value Algorithm. Fixed isse where driver would get into endless loop when writing to a not responsive device. Driver now requires .NET 4. Updated driver installer to work with win 64 bit. Driver service now is a dependency of the SQLSERVER service. Renamed the ModbusDriver service to qModbusDriver service. ******************************************************************************** InetSupervisor Release date May 1, 2014 InetSupervisor version: 140501 HMI Web Portal May 1, 2014 qConcentratorService.exe 14.2.24.80 DatabaseConfig.exe 13.11.8.22 qInetDriverService.exe 13.11.6.75 LNSConfig.exe 13.9.27.54 qLNSDriverService.exe 14.4.10.446 qModbusDriverService.exe 13.9.29.7 TitanSDKService 1.0.0.0 Added monitor set functionality to LNS driver, Added automatic graphics generator to HMI web portal Added WebEditor, a replacement for DreamWeaver to HMI web portal Added new licensing options to handle third party apps in HMI web portal ******************************************************************************** InetSupervisor Release date June 11, 2010 InetSupervisor version: 100611 Concentrator ServiceAtlas 10.5.17.0 DBConfig 10.6.11.0 InetDriver 10.5.20.0 LNCConfig 2.0.0.28326 LNSDriverService 2.0.0.38204 ModbusDriver 1.0.0.0 OPCConfig 1.0.0.0 OPCDriverService 1.0.0.0 TitanSDKService 1.0.0.0 Added RTS handling to SolidyneDriverService. Now the driver should work OK with M202 interfaces and be more stable with M204. ******************************************************************************** Release_Atlas May 20, 2010 Fixed InetDriver bug that prevented overrides from working reliably. Requires InetDriver and HMI WEB update. ******************************************************************************** Release_Atlas May 19, 2010 Updated InetDriver did not make it in the May 18 release. Its now updated in the May 19 CD ******************************************************************************* * Release_Atlas May 18, 2010 Implemented program/file versions. Updated SolidyneDriver to reset COM port on errors, fixed reding of negative number. Negative numbers used to be offset by +1. Fixed a bug in ScheduleEditor where user could not enter proper time in exceptions. Added a mini schedule editor which allows for schedule editing specific to a piece of equipment. Watch video on InetSupervisor.com for details. Added Optimum Start functionality for any scheduled point. Open OSS editor from PointsEditor. ConcentratorService reboots SolidyneDriver hourly if driver has been running. Improved TrendViewer performance and compression. Simplified InetDriver security and connection to remote Rheas. ******************************************************************************* Release_Atlas September 17, 2009 Updated HMI Web with the speed related improvements for flash components with multiple points within single swf. Modbus Driver - fixed a bug that prevented writing device in some cases. HMI Web - added Active Alarm Count display to the navigation tree. ******************************************************************************* Release_Atlas July 10, 2009 Added McQuay alarm handling flash component into FX/001/McQuay. Use it to translate alarms encoded into SNVT_Switch to a readable text. Updated LNS Config -> LonWorksTypes.xml to recognize more Distech gFx structured points. ******************************************************************************* Release_Atlas May 20, 2009 OPC driver - bug fix with evaluation version popup ConcentratorService feature activated where we now can turn off delivery of alarms on a point-by-point basis in the point editor/ alarm config HMIWeb bug fix on web site login, before the system would require that you login twice. ******************************************************************************* Release_Atlas June 2, 2009 HMI Web - fixed schedule editor bug where assignment of schedules to point would fail ******************************************************************************* Release_Atlas April 25, 2009 Licensing has changed. All updates are free for 12 months after we issue a license. Added InetDriver service, This is InetSupervisor Enterprise driver. InetDriver allows you to transfer data between different InetSupervisors. This version now requires .NET version 2.0 and 3.5 SP1, make sure you install the .NET 3.5 SP1. The HMI web requires crossdomain file in the wwwroot directory for the Enterprise features to work. This file must be placed there by hand. Placing the Crossdomain file in your web directory (wwwroot)allows external FLASH components to establish communications with your server and exposing it. We updated the navigation tree, tree editor, schedule editor, login page to ENTERPRISE version. Many viewers and editors have been updated to rescale with the browser. Added Modbus RTU serial , and TCPIP driver. The Modbus driver comes with a web-based ModbusConfig, so the update of HMI WEB is necessary. Trending now supports sub-OneMinute interval. For example in the DB Config/config table you can enter 0.5 for the Trends 0 Interval to get 30 second updates. HMIweb now supports Enterprise features. You can edit the tree to show web pages from multiple Rheas. You can also edit schedules all at once on multiple RHEAS. To use the Enterprise features you need to enter IP addresses into the DDNS table (InetLogs.WhatsMyIp) for all Rheas. Once the IP addresses are entered you also get the Enterprise login to all sub-rheas. Schedule Editor is now capable of editing schedules on multiple Inets in the enterprise. Graphical editing was added to the Schedule Editor. DBConfig will adjust the LonDigON and LonDigOFF column width making it possible to use the SNVT TOD. ******************************************************************************** Release_Atlas September 15, 2008 BACnet driver, BacnetConfig, cWinDemo - improved performance and compatibility with BACnet IP devices. ************************************************************************************* Release_Atlas September 2, 2008 We added a new driver. This driver is an OPC client that is capable of talking to OPC servers. We now provide TAC Inet OPC server as one of the OPC server solutions. The OPC client (Our product) is a NO COST item. The OPC Servers come with a price tag. Refer to your price list for details. We also posted a video how to use the driver. Dont forget to install OpcRuntime and read the PDF (located in OpcRuntime.rar) for DCOM related instructions. ************************************************************************************** Release_Atlas August 15, 2008 HMIweb - added Enterprise Navigation MAP example in the DEMO subfolder of the HMI virtual directory. See source of the "map.aspx". You can setup InetSupervisor to start at http://127.0.0.1/hmi/demo/map.aspx to see it at work. Right click on a pin to navigate to the site. Edit the XML file to include your locations. ************************************************************************************** Release_Atlas July 14, 2008 HMI web was updated to make Vista work with InetSupervisor web pages. In some instances the web pages of HMI framework apeared blank. Now the framework web pages use scrip from the latest Dreamweaver CS3. Trend viewer was tripping when database had inconsistent data. Now its immune. ************************************************************************************** Release_Atlas June 23, 2008 Trend Viewer now supports all trend databases. You now can also download trend data from the web directly into a CSV file. Changes in: hmi, wsconfig, concentrator, dbConfig ************************************************************************************** Release_Atlas June 9, 2008 This is a most significant speed update for the web page framework to date. Now the values in flash components show up instantly. ConcentratorService now has a fully implemented trend compression. Next update should bring the updated TrendViewer that will allow for viewing of compressed data. PointEditor now has a Point Override functionality ************************************************************************************** Release_Atlas May 19, 2008 Added support for Dynamic DNS. Now the InetSupervisor can be hosted on an DHCP network while maintaining accessibility from the Internet. Added new TrendViewer web application. It provides data download functionality and a fresh look. Now the ConcentratorServiceAtlas and the LNSDriverService installs with startup type set to MANUAL. You need to change the service startup type AUTOMATIC for production. ************************************************************************************** Release_Atlas March 15, 2008 Now the Alarm Manager plays a sound when an alarm is detected. LNSConfig now can write config properties with delimited values (global override). This is very useful when for example commanding all Distech VAVs to persist schedules you set and property as UCPTdeviceOptions, delimiter as a space, position as 45 , and value as 1. Solidyne Driver: added support for UI Override trigger and cancel. Improved the Alarm Manager to show site name (as set in Config Table) *************************************************************************************** Release_Atlas Feb 15, 2008 SolidyneDriver - added support for decimal places in Solidyne Virtual points. HMI WEB - Added DEMO pages. These pages install automatically with the HMI WEB and are accessible through the navigation tree. They are based on InetSupervisor Virtual Points that can be added using PointEditor on the web. *************************************************************************************** Release_Atlas November 5, 2007 ConcentratorService_Atlas - added properties to Config table for customizing the alarm e-mail SUBJECT line and the FROM address. *************************************************************************************** Release _ Atlas Oct 26, 2007 SolidyneDriver - improved performance. LNS Config - added handling for WriteArgs, ReadArgs. HMIweb - Fixed a bug in Schedule Editor that would delete more schedules when deleting a single schedule. *************************************************************************************** Release _ Atlas Oct 2, 2007 SolidyneConfig is now revised by Solidyne. It should handle import of points from the new style databases. SolidyneDriver now requests updates for all nodes even if you import points from higher node IDs skipping low node id devices. Now the LNSDriverService understands WriteArgs in addition to ReadArgs, see web PointEditor for more. Fixed schedule handling bug in the new ConcentratorServiceAtlas. *************************************************************************************** Release - ATLAS August 22, 2007 Updated SolidyneDriver to send update requests to all nodes every 5 min. Provided new Alarm viewer. Provided new User editor. Updated Tree Editor to write tree structure to qTreeNodes0.xml directly to server(w/o concentrator) *************************************************************************************** Release - ATLAS May 22, 2007 Updated page sysapp\qChartByID.aspx?PointID=123,456,789 Use this syntax to show a great looking chart. Fixed bug that prevented TrendsOther web page from working in certain circumstances. Fixed a bug that prevented some points from updating in SolidyneDriver. Release - ATLAS June25, 2007 HMIWEB was upgraded with a workaround for MS "Update" that corrupts handling on post back messages. This issue resulted in duplicate trend entries showing in the trend page. **************************************************************************************** Release - ATLAS March 27, 2007 Login page changed to support login without keyboard. Licensing changed to be more compatible with multi-core systems. LNSDriver now does not request updates automatically after writing a variable. This became a problem on very large networks. Defaults changed in the config table. Now the default trend interval starts at 15 minutes, also the AllPointsUpdateInterval is -1 which disables all points auto update. **************************************************************************************** Release - ATLAS Feb 28, 2007 Added flash components related to Solidyne networks. These are located in the hmi/FX/Sol web folder. Expanded functionality of the TreeEditor. Now you can see all existing files in one tree and drag files or entire folders into the navigation tree. ***************************************************************************************** Release - ATLAS Feb 21, 2007 Fixed QTreeEditor.fla - tree Editor that in certain conditions would not write the tree back to the server. The bug affected only the Feb 14 release. Fixed FX-RealTimeTrend.fla - real time trends. The bug affected only Feb 14 release. **************************************************************************************** Release - ATLAS Feb 14, 2007 – MAJOR UPGRADE To upgrade previous version to this release you must uninstall the previous version completely including the Database Server “Sql Server Desktop Engine”. Make sure you keep a good backup of the working system. - HMIWEB is reorganized with sub folders to keep a clean structure. There is a new web page qChartByID.aspx. This page provides new style trend visualization. You should call this page by sysapp/qChartByID.aspx?PointID=111,222,333 where the 111 etc are the PointIDs of trend able points delimited by commas. - DB Config, fixed a bug that in some cases made the databases read-only. -PointEditor now can configure an algorithm that will calculate PointValue from the RAW -Network value. This includes add, subtract, multiply, divide, Cos, tan, limit decimal places -Now we include new utility "Dreamweaver Flash Config" installer is located in c:\inetpub\wwwroot\HMI\sysapp\flash\QCI Flash Config.mxp. Once installed it allows for doing the following within the Dreamweaver: pick PointID, configure background colors, borders, fonts, min and max for gauges, etc. -sql server was upgraded to latest 2005 version. LNSDriverService was updated to work with sql server 2005 SolidyneDriver was updated to work with sql server 2005 The CD now contains server management application in the Other Utilities folder. **************************************************************************************** Release December 6 2006 Flash Schedule Editor - Fixed bug in daily schedule start time box to allow change of time for new schedule, **************************************************************************************** Release Dec 3, 2006 SolidyneDriver- implemented support for IO FORCING. Implemented support for extended virtual points. Now you can read and write virtuals 1-16. **************************************************************************************** Release Oct 29, 2006 TEAM - ordered Tenants alphabetically. Concentrator - Implemented Global-Holidays. HMIWeb - Updated schedule editor with navigation tabs and access level checking. SolidyneConfig - Added buttons to import multiple points. ***************** Release Oct 15, 2006 Fixed a number of bugs in Solidyne Driver. **************************************************************************************** Release Oct 2, 2006 Added support for multiple LNS networks. The CD contains LNSDriverService2. Use it to work with a second LNS network. Kits for instances 3,4,5,etc. are available upon request. Added support for proprietary Solidyne networks. Alarms page is now sorted from latest to oldest alarm. Also the column headers when clicked sort alarms. **************************************************************************************** Release July 31, 2006 HMI web only Fixed decimal precision bug in Fx-PtVal-20x80-alg.swf New flash symbols for wait, trend, and alarm. New symbols cause less trips to and from server to lessen bandwidth utilization and increased speed. **************************************************************************************** Release June 26, 2006 HMI web only. New feature, PointEditor. Now you can click in any flash component's text box, then press the TAB and the "C" key simultaneously to bring up the PointEditor for the particular point (Configure a point). You can bring up the PointEditor from the tree as well and choose a point. Now also you can press "TAB" and "I" keys for point information. You will see a pop-up box appear with the info. ***************************************************************************************** Release June 15, 2006 Fixed a bug introduced in June 12 release where the c:\LonWorks\Apps\QCI\Logs directory was missing causing services to fail ***************************************************************************************** Release June 12, 2006 Added iLON100 Soap Driver Service. Use it to backup trend data from iLON100s to InetSupervisor's SQL Server database. You can then use InetSupervisor to plot graphs on the web. Added on-start delay to LNSDriverService and ConcentratorService to prevent the services from starting while the SQL Server is not available yet. (SQL Server service takes longer to start). ***************************************************************************************** Release June 6 2006 Flash Update only. Fixed bug in flash. Analog values of less than 1 and greater than 0 will now display the proper value if decimal place limiting is used. ***************************************************************************************** Release May 31 2006 HMIWeb added functionality to flash to allow the displayed digital values to be user defined. HMIWeb added functionality to flash; pop-up box will appear with Logical Name, Point ID, Channel Name, and Device Name. See Flash_User_Guide.pdf for details ***************************************************************************************** Release May 8, 2006 HMIWeb added web page to the aspx framework that can be used to show trends for points that are not a number, such as SNVT Occupancy, etc. Expanded Flash Users Guide. Improved Install Shield installers, added checks for IIS, and LNS runtime. ***************************************************************************************** Release April 28, 2006 LNSConfig is now capable of parsing UNVTs as structured variables. Flash Components- improved load speed for all components. Improved Tree Editor. Now you can navigate the tree with arrow keys, and enter. InetTEAM now works as a .NET 2.0 application (upgraded from .NET1.1) Concentrator - improved alarm e-mail management. Now you can send alarms to users with specified range of alarm levels. ( less than, greater than) LNSDriver_installer now checks for LNS turbo, and warns if not existing. ***************************************************************************************** Release Mar 7, 2006 HMIWeb now uses xml-based navigation tree. New FX series flash components are located in the FX subdirectory. Now including gauges, thermometers, wall sensors, etc. Added many new features to flash components. Updated User's Guides are now located in c:\inetpub\wwwroot\hmi\help LNSConfig Graphics Generator now works with Structured SNVTs. ***************************************************************************************** Release Feb 7, 2006 Modified the installer to be compatible with .NET framework V. 2.0. Found and documented error that occurs during upgrade to .net 2.0. See tech bulletin on www.InetSupervisor.com/manuals